CPMC Panel-Panel Filters-BEIJING AIHE NUCLEAR POWER TECHNOLOGY CO.,LTD.



      WELCOME TO BEIJING AIHE NUCLEAR POWER TECHNOLOGY CO.,LTD. !

      • 中文版
      • English

      SPECIFICATIONS

      Application: HVAC 

      Frame: Galvanized steel 

      Spacers: Hotmelt 

      Bonding: 2 component polyurethane 

      Media: Glass fibre paper 

      Gasket: Continuous poured gasket

      Filter class according to EN779:2012: M5, M6, F7 and F9

      Maximum/recommended final pressure drop: 450Pa

      Maximum temperature: 65°C

      Maximum relative humidity: 90%

      Comments: possibility to deliver T-profile for mounting two

      frames together


      ADVANTAGES

      • Compact construction

      • Firm construction


      DETAIL


      Qualities

      AFPRO panel filters are pleated filters which are characterised by their superior filtration 

      properties. The synthetic filter medium is progressively constructed, which makes for a high 

      particle interception level. This technology guarantees lower air resistance, which also

      entails reduced energy consumption.


      Advantages of panel filters

      • Large filter surface

      • High particle interception capacity

      • Lengthy service life

      • Low energy consumption

      • Dimensions compliant with EN15805

      • Moisture-resistant cardboard frame

      • Completely safe for incineration


      Construction

      Panel filters are pleated filters which are assembled within a moisture-resistant cardboard 

      frame.


      Application

      Panel filters are used as a pre-filter for air treatment cabinets, air conditioning systems 

      and industrial systems.


      Installation

      • Ensure that the filter is fitted correctly:Suction side – clean air side

      • Filter should be correctly installed: no leaks

      • Gaskets should be completely undamaged

      • Filter should be secured at four points

      • Ensure that the filter medium is not folded double

      • Take care to avoid damaging the filter during installation

      • System should be run in for several hours to achieve the desired result

      • Filter installation records; note the date, type and initial resistance.





      BACK